GB200 NVL72, GB300 NVL72, and Vera Rubin NVL72 are the three racks any NVL72 HBM capacity comparison has to cover, and each shipped with more HBM than the rack before it. That's the headline most coverage leads with, and it's true: 13.4TB, then 20TB, then 20.7TB per rack. What almost nobody says is that the number actually gating how large an MoE expert-parallel group can scale, the NVLink domain size, hasn't moved at all across those three racks. It's been fixed at 72 GPUs since Blackwell shipped, through two full NVLink generations.
That distinction matters if you're sizing a rack reservation around a mixture-of-experts model rather than a dense one. This post separates what actually changed (HBM capacity, HBM type, NVLink bandwidth) from what didn't (domain size), and names the one system that will actually move it: Rubin Ultra's Kyber rack, which isn't shipping until 2028.
TL;DR: NVL72 HBM Capacity Comparison, GB200 vs GB300 vs Rubin
- GB200 NVL72: 72 B200 GPUs, 13.4TB total HBM3e (186GB/GPU in-rack), one 72-GPU NVLink 5 domain at 130TB/s, per NVIDIA's GB200 NVL72 spec page.
- GB300 NVL72: 72 B300 GPUs, 20TB total HBM3e (288GB/GPU), same 72-GPU NVLink 5 domain at 130TB/s, per NVIDIA's GB300 NVL72 spec page.
- Vera Rubin NVL72: 72 Rubin GPUs, 20.7TB total HBM4 (288GB/GPU at 22TB/s), still a 72-GPU domain, now on NVLink 6 at 260TB/s.
- Domain size: unchanged at 72 GPUs across three racks and two NVLink generations. The jump happened one generation earlier, Hopper's 8-GPU NVLink 4 domain to Blackwell's 72-GPU NVLink 5 domain.
- The real jump: Rubin Ultra's Kyber rack doubles the domain to 144 GPUs, but it slipped from 2027 to 2028.
- Spheron takes reservations on GB200 NVL72 and GB300 NVL72 today, with Vera Rubin open for pre-order; B200 and B300 rent on-demand right now for workloads that fit a single node.
What NVLink Domain Size Actually Controls (and Why It Isn't the Same as GPU Count)
NVLink domain size is the number of GPUs that can reach every other GPU in one hop, at full NVLink bandwidth, through a shared NVSwitch fabric. It is not the same thing as how many GPUs sit in your cluster. A training job can span 32,000 GPUs, but those GPUs are organized into many separate NVLink domains, each one a rack, connected to each other by InfiniBand or Ethernet instead of NVLink. Traffic that stays inside one domain moves at terabytes per second in a single switch hop. Traffic that crosses domain boundaries drops to whatever the inter-rack network provides, and usually takes more than one hop to get there. Our NVLink explainer covers the PCIe-versus-NVLink gap in more detail if you need that foundation first.
NVIDIA's own description of GB200 NVL72 calls it "a single 72-chip domain", and is explicit that a larger domain is possible with additional switch tiers, up to 576 GPUs at over 1 PB/s of aggregate bandwidth. That 576-GPU figure describes a different, larger topology than the 72-GPU rack sold as the standard NVL72 product; it is not what ships when you reserve a GB200, GB300, or Vera Rubin NVL72 rack today. The rack-scale product's domain is 72 GPUs, full stop.
How a 72-GPU NVLink Domain Is Physically Built
The 72-GPU figure isn't a software limit NVIDIA chose for marketing. It's set by how many GPUs one tier of NVSwitch ASICs can wire together before a second tier becomes necessary. A GB200 NVL72 rack carries nine NVLink switch trays, and each of the 72 GPUs connects to every one of them over a copper backplane, giving every GPU a full-bandwidth path to every other GPU in exactly one hop. GB300 NVL72 and Vera Rubin NVL72 keep that same nine-tray layout; only the GPU module and the switch generation inside each tray change.
Why Nine Switch Trays, Not One Big Switch
Inside a single rack, NVIDIA runs NVLink over copper wherever it can: the GB200 NVL72 backplane keeps the 72-GPU domain on copper at the rear of the cabinet, which saves roughly 20kW per rack against optical links and keeps latency lower. That copper reach doesn't carry between racks, though. Once NVLink has to cross a rack boundary, copper reach runs out and the link switches to optical modules instead, which is what turns a cluster bigger than one cabinet's worth of domain into multiple 72-GPU domains stitched together over a slower fabric. Nine switch trays is how many NVSwitch tiers NVIDIA fits inside one cabinet at this generation; reaching further within the rack, or doubling the GPU count to 144 the way Rubin Ultra's Kyber rack is attempting, means redesigning the backplane itself rather than bolting on a tenth identical tray.
That redesign is what's actually behind Kyber's delay, and it isn't down to copper reach alone. Kyber slipped more than 12 months, from an original 2027 target to 2028, over manufacturing difficulty with the rack's 78-layer PCB midplane, and SemiAnalysis's reporting on the slip names several compounding factors inside that one board: signal integrity, power delivery, thermal design, and the manufacturable layer counts needed to build a PCB with 78 layers at all, not a single root cause.
From 8-GPU Domains to 72: A Short History of NVLink Domain Size
Domain size didn't climb steadily generation over generation before Blackwell; it actually shrank first. NVIDIA's first NVSwitch chips, in the 2018 DGX-2, wired 16 Volta GPUs into one full-mesh domain. The following Ampere generation's DGX A100 stepped that down to 8 GPUs across six second-generation NVSwitch ASICs, and Hopper's DGX H100 held at that same 8-GPU domain with third-generation NVSwitch silicon two years later, per Fibermall's history of NVLink and NVSwitch generations. Blackwell is what broke the pattern, jumping straight from an 8-GPU domain to 72.
| Generation | System | GPUs per NVLink domain | NVSwitch generation | Per-GPU NVLink bandwidth |
|---|---|---|---|---|
| Volta | DGX-2 | 16 | 1st-gen | 300GB/s |
| Ampere | DGX A100 | 8 | 2nd-gen | 600GB/s |
| Hopper | DGX H100 | 8 | 3rd-gen | 900GB/s |
| Blackwell | GB200 / GB300 / Vera Rubin NVL72 | 72 | 5th-gen (6th-gen for Vera Rubin) | 1.8TB/s (3.6TB/s for Vera Rubin) |
Measured as a jump rather than a crawl: eight GPUs per domain for six years running, then 72 practically overnight. That's the context most GB200-to-GB300-to-Rubin comparisons skip. The real step change in domain size already happened, and it happened once.
NVL72 HBM Capacity Comparison: GB200 vs GB300 vs Vera Rubin, Side by Side
| Rack | GPU | HBM type | HBM per GPU | Total rack HBM | NVLink generation | NVLink per GPU | Rack switch bandwidth | NVLink domain size |
|---|---|---|---|---|---|---|---|---|
| GB200 NVL72 | B200 | HBM3e | 186GB | 13.4TB | NVLink 5 | 1.8TB/s | 130TB/s | 72 GPUs |
| GB300 NVL72 | B300 | HBM3e | 288GB | 20TB | NVLink 5 | 1.8TB/s | 130TB/s | 72 GPUs |
| Vera Rubin NVL72 | Rubin | HBM4 | 288GB | 20.7TB | NVLink 6 | 3.6TB/s | 260TB/s | 72 GPUs |
The GB200 row comes straight from NVIDIA's GB200 NVL72 spec page, the GB300 row from NVIDIA's GB300 NVL72 spec page, and the NVLink-generation bandwidth figures from GPUSmith's NVLink 5 vs NVLink 6 comparison.
Two things stand out reading this table left to right instead of generation to generation. First, GB300 and Vera Rubin land on an identical 288GB-per-GPU figure despite being different memory generations (HBM3e versus HBM4), which is why the real differentiator between those two racks is bandwidth, not capacity: Vera Rubin's HBM4 runs at 22TB/s per GPU against GB300's 8TB/s HBM3e. Second, and the point of this whole comparison, the rightmost column never changes. Every rack in this table is a 72-GPU domain. GB200 NVL72's full rack spec table and the deeper GB300 vs GB200 pricing and availability comparison cover the compute-side differences this table leaves out (dense FP4 throughput, FP64, networking, and rack power and liquid cooling requirements), if you're deciding between those two specifically.
One figure worth flagging on its own: a standalone B200 card is rated at 192GB of HBM3e, not the 186GB shown above. NVIDIA publishes 186GB specifically for the per-GPU figure inside the NVL72 rack configuration, and conflating the two is a common error in rack-spec writeups.
Power and Cooling Scale With HBM, Even Though the Domain Doesn't
More HBM and a newer memory type don't arrive for free. Each generation's GPU module runs at a higher thermal design power, and the rack's total draw climbs with it even though the GPU count and domain size stay fixed at 72.
| Rack | TDP per GPU | All-in power per GPU* | Total rack power | Cooling |
|---|---|---|---|---|
| GB200 NVL72 | 1,200W | ~1.87kW | ~135kW | Fully liquid-cooled |
| GB300 NVL72 | 1,400W | ~2.12kW | ~153kW | Fully liquid-cooled |
| Vera Rubin NVL72 | Not yet published | Not yet published | Not yet published | Expected fully liquid-cooled |
\*All-in power includes each GPU's share of the host CPU, NICs, and cooling overhead, per SemiAnalysis InferenceX's GB200 NVL72 and GB300 NVL72 power breakdowns. SemiAnalysis publishes the per-GPU TDP and all-in power figures only; the total rack power rows above are this post's own arithmetic, that all-in per-GPU figure multiplied by the rack's 72 GPUs, not a rack-level total SemiAnalysis itself states. Vera Rubin hasn't published a rack-level power figure yet, which tracks with where it sits commercially: it's still a pre-order product, not something any provider is quoting a power envelope for today.
Power draw varies by data center partner, region, and actual rack configuration, so treat the GB200 and GB300 rows above as representative rather than exact. Check with the data center partner or provider sourcing your reservation for the power envelope that applies to your specific deployment.
The pattern holds across every generation in this comparison: HBM capacity, chip TDP, and total rack power all move together, while the number of GPUs sharing one NVLink domain doesn't move at all. If you're budgeting data center power alongside a rack reservation, the capacity row in the table above and the power row here come from the same generational jump. The domain-size column doesn't.
Why Domain Size Matters More for MoE Models Than Dense Ones
A dense model shards its one set of weights across GPUs with tensor or pipeline parallelism, and the communication pattern is predictable: mostly neighbor-to-neighbor, with an occasional all-reduce. A mixture-of-experts model has a different problem. Every token has to be routed to whichever experts it was assigned to, which are scattered across GPUs, and the result is a genuinely all-to-all communication pattern at every MoE layer, not an occasional one.
That's where domain size stops being an abstraction. When an expert-parallel group fits inside one NVLink domain, every GPU-to-GPU hop in that all-to-all shuffle stays on the switch fabric. When it doesn't, the group gets forced onto InfiniBand instead, multi-hop, at a fraction of the bandwidth, and that's reportedly why GB200 and GB300's one-hop, all-to-all 72-GPU fabric is what lets these racks dominate wide-expert-parallel serving of large MoE models in the first place, according to SemiAnalysis's InferenceX analysis.
NVIDIA's own numbers back up how much that's worth: it credits the 72-GPU NVLink domain with a 30x inference speedup on a 1.8-trillion-parameter GPT-MoE model at FP4, and 4x faster training on a 32,000-GPU GB200 NVL72 cluster, versus equivalent H100 deployments. A real MoE training run backs this up outside NVIDIA's own marketing, too: Reflection AI pretrained its 501B-parameter MoE model, Beam, on 6,144 GB300 NVL72 GPUs in under four weeks at 92.3% goodput, roughly 85 full 72-GPU domains' worth of hardware stitched together, a workload our Beam deployment walkthrough covers in more depth. A dense model at that same GPU count would care far less about where the domain boundaries fall.
Worked Example: Sizing an Expert-Parallel Group Against Rack HBM
The abstract version of "does my expert-parallel group fit in one domain" is easier to answer with real parameter counts than with another spec table.
Example 1: A 671B-Parameter MoE Model at FP8
DeepSeek-V3 carries 671 billion total parameters, with 37 billion active per token, and its experts are a natural fit for sharding one-per-GPU across an NVLink domain. Stored at FP8, a common quantization choice for inference, the full 671B-parameter weight set takes roughly 671GB. Spread evenly across a 72-GPU NVL72 domain, that's about 9.3GB of weights per GPU. On GB200 NVL72's 186GB per-GPU HBM budget, that leaves roughly 177GB per GPU free for KV cache, activations, and framework overhead, all without the expert-parallel group ever leaving the one-hop NVLink fabric. On GB300 NVL72's 288GB per GPU, that same 9.3GB of weights leaves close to 279GB free, nearly 60% more headroom for KV cache inside the exact same 72-wide domain.
Example 2: What a Dense 405B Model Needs, By Comparison
Contrast that with a dense model of similar size. Meta built Llama 3.1 405B as a standard decoder-only transformer rather than a mixture-of-experts model, so there's no routing step and no all-to-all shuffle to keep inside one domain. Tensor-sharded across just 8 GPUs at FP8, its 405B parameters work out to roughly 50.6GB per GPU, comfortably inside even a single Hopper-era 8-GPU NVLink domain, let alone a 72-GPU Blackwell one. That's the concrete version of the claim above: the MoE model needs the 72-GPU fabric to keep its routing fast, and a dense model of similar size barely needs the smallest domain NVIDIA still sells.
The Domain Size Jump Nobody's Renting Yet: Rubin Ultra's Kyber NVL144
If the goal is a bigger NVLink domain, not just more HBM inside the same 72-GPU domain, the system to watch isn't base Vera Rubin. It's Rubin Ultra, which ships in NVIDIA's new Kyber rack at NVL144 scale, doubling the GPU-package domain to 144 versus Vera Rubin NVL72's 72. NVL576 goes a step further, linking eight Kyber racks together over co-packaged optics into one larger pod.
That's the domain-size jump that actually matters for MoE expert-parallel scale, and it's not available to rent anywhere yet. Kyber slipped more than 12 months, from an original 2027 target to 2028, reportedly over manufacturing problems with the rack's 78-layer PCB midplane. Our Kyber delay writeup goes through what NVIDIA has and hasn't confirmed about that slip. Until Kyber actually ships, GB300 NVL72 and Vera Rubin NVL72 are the ceiling on domain size that any cloud customer can book, and that ceiling has been 72 GPUs since Blackwell launched.
Rubin CPX NVL144: A Different 144-GPU Rack, Shipping Before Kyber
A second NVIDIA rack also carries the "NVL144" name, and it's easy to confuse with Rubin Ultra's Kyber system covered above. It isn't the same product, and it isn't on the same timeline.
Rubin CPX is a GPU built specifically for massive-context processing, the compute-heavy prefill phase of serving requests with million-token contexts, such as long-document coding assistants and generative video. It ships inside the Vera Rubin NVL144 CPX platform, pairing CPX GPUs, each carrying 128GB of GDDR7 rather than HBM, with standard Vera CPUs and Rubin GPUs in a disaggregated-serving rack: CPX handles the prefill phase, and regular Rubin GPUs handle the memory-bandwidth-heavy decode phase. NVIDIA says the rack delivers 8 exaflops of AI compute, 100TB of fast memory, and 1.7 petabytes per second of memory bandwidth, which it positions as 7.5x more AI performance than a GB300 NVL72 system, with 3x faster attention processing than GB300.
What CPX Doesn't Change
CPX's "144" describes a disaggregated rack built from two different GPU types split across two serving phases, not a single, homogeneous 144-GPU NVLink domain the way Kyber's NVL144 is designed to be. It also arrives much sooner: NVIDIA expects Vera Rubin NVL144 CPX racks by the end of 2026, more than a year ahead of Kyber's delayed 2028 date. If you're tracking when the NVLink domain size itself next moves past 72 GPUs for a homogeneous expert-parallel group, Kyber is still the date to watch, not CPX.
When a Bigger Domain Actually Changes Your Rental Decision
The memory increases from GB200 to GB300 to Vera Rubin are real and useful on their own: more HBM per rack means a bigger model, or more KV cache headroom, fits inside one domain before you need to cross a domain boundary at all. But if your MoE model's expert-parallel group already fits inside a 72-GPU domain, GB300's extra 6.6TB over GB200, or Vera Rubin's extra bandwidth over GB300, doesn't change your scale-out ceiling. It just means you hit that ceiling with more memory to spare. The domain-size decision and the HBM-capacity decision are two separate questions, and conflating them is the mistake most rack-spec comparisons make.
Spheron reserves GB200 NVL72 and GB300 NVL72 capacity from a single node up to a full 72-GPU rack, sourced from its data center partner network, with Vera Rubin open for pre-order ahead of its H2 2026 ship date. None of the three carry a published hourly rate; reservation requests typically come back with a sourced quote within 24 to 48 hours. If your model fits inside a single 8-GPU node's worth of domain, a non-rack B200 or B300 cluster is cheaper and faster to provision than reserving rack-scale capacity for headroom you won't use, a tradeoff our GB300 NVL72 vs single B300 GPU breakdown covers with a full rent-or-reserve checklist, and both rent on-demand today at $10.17/hr and $11.52/hr respectively. And if what you actually want is a domain bigger than 72 GPUs, there's no honest answer to give you yet. Rubin Ultra's 144-GPU Kyber domain isn't reservable from any provider, Spheron included, and isn't expected before 2028.
Pricing fluctuates based on GPU availability. Spheron rates above are live as of 12 Nov 2026; other providers reflect their most recent published rates and may have changed. Check current GPU pricing → for live rates.
Rack-scale NVLink domain stays at 72 GPUs through GB200, GB300, and Vera Rubin, so the HBM capacity gains are worth having, but they won't change your expert-parallel ceiling. Reserve GB200 NVL72 or GB300 NVL72 capacity, or rent B200 and B300 on-demand today.
Frequently Asked Questions
NVLink domain size is the number of GPUs that can reach every other GPU over the NVLink switch fabric in a single hop, at full NVLink bandwidth, without crossing onto InfiniBand or Ethernet. It's a property of the switch topology, not a count of GPUs in a cluster. A cluster can span thousands of GPUs across many separate NVLink domains, each stitched together by a slower, multi-hop network fabric.
13.4TB total across the rack, from 72 B200 GPUs at 186GB of HBM3e each in the NVL72 configuration, per [NVIDIA's GB200 NVL72 spec page](https://www.nvidia.com/en-us/data-center/gb200-nvl72). A standalone B200 card is rated at 192GB; 186GB is specifically what NVIDIA publishes for the per-GPU figure inside the NVL72 rack.
Yes. GB300 NVL72 swaps in B300 Blackwell Ultra GPUs at 288GB of HBM3e each, for 20TB total per rack, against GB200's 13.4TB. Both racks still run the same 72-GPU NVLink 5 domain at 130TB/s of switch bandwidth, so the memory increase doesn't change how many GPUs can talk to each other in one hop.
No. Vera Rubin NVL72 holds the domain size at 72 GPUs, the same as GB200 and GB300. What changes is memory type and interconnect speed: 288GB of HBM4 per GPU at 22TB/s (20.7TB per rack), and NVLink 6 at 3.6TB/s per GPU, double NVLink 5's 1.8TB/s, for 260TB/s of rack-level switch bandwidth, per [GPUSmith's NVLink 5 vs NVLink 6 breakdown](https://gpusmith.com/articles/en/nvlink-5-vs-nvlink-6). The domain itself is still 72 GPUs wide.
Rubin Ultra NVL144 is the first rack-scale system to actually double the NVLink domain, to 144 GPU packages, inside NVIDIA's new Kyber chassis. NVL576 goes further, linking eight Kyber racks into one larger pod over co-packaged optics. Kyber slipped more than 12 months, from an original 2027 target to 2028, reportedly over manufacturing problems with its 78-layer PCB midplane. No provider, Spheron included, has a rentable NVL144 domain today.